Botched Room Soundproofing

A contractor contacted me to test the sound transmission loss (STC value) at his newly built high-security conference room and confirm that the room's soundproofing meets the client’s requirements for STC 55. The test failed.

More...



The construction of the high-security conference room was completed without prior acoustic expert advice about room soundproofing. The contractor installed walls with STC 68.  The assembly is listed in the Ontario Building Code as assembly no. S14a (Fig. 1).

Figure 1 - Staggered stud wall

Room soundproofing test results

I have tested three walls; one was original and not affected by the construction. The layout of the space is in Fig. 2.

Figure 2 - Floor plan of the tested conference room

The test results were STC 54, STC 47, and STC 28, all failing the project requirements of STC 55. The contractor was distraught; he thought he had built it for STC 68.

Soundproofing defects.

The contractor was unaware of the flanking noise paths and did not take the necessary steps to mitigate them. Most contractors make this mistake with room soundproofing, neglecting to consult an acoustic engineer before construction.

The defect causing STC 28.

The wall (see Fig. 2) has a door in it.  Most standard doors, when perfectly sealed, have STC 30 to 35.  No door is perfectly sealed.  The door is the weakest acoustic part of the wall and dominates the test results, causing STC 28.

The defects causing STC 47 and 54 in room soundproofing.

The conference room has a large rectangular duct in the plenum above its ceiling (dashed lines in Fig. 2).  The duct penetrates both side walls, causing a large opening (Fig. 3). A steel rectangular duct has a low resistance to break-in noise, which exists on the other side of the wall as break-out noise. Additionally, the thermal insulation around the duct prevents the drywall from sealing correctly against the duct, further aggravating the problem.

Figure 3 - Duct through the conference room side wall causing a defect in room soundproofing.

Fixing the problem in the room soundproofing.

It is not possible to achieve STC 55 for the door. The only solution is to replace it with a special acoustic door. This is a problem when the customer wishes all doors to appear the same.

Enclosing the ducts in the plenum above the conference room in a drywall duct chase can mitigate the noise path through its openings in the walls.

Fixing a botched room soundproofing is always more expensive than doing it right the first time with the advice of an acoustic engineer.

We will respond quickly with our no-obligation quote.
Your personal information is not stored online.

We always appreciate your feedback. Please use the form below to contact us.

About the Author Ivan Koval

The author is the publisher of the Soundproofing.Expert website. He is a soundproofing and building acoustics consultant working in Toronto and GTA, Ontario, Canada. Telephone (416) 471-2130

Follow me

↓